Cassette fancoil unit ATTACK FCU

Suitable for heat pumps

Category:

2-24 kW
Power

Comfortable temperature
all year round

3
Step modulation

Automatic
Flap rotation

Cassette fancoil units with power from 2 – 24 kW are suitable for larger spaces where they ensure a pleasant temperature all year round. It is precisely the heat pump as a source of heat and cold that can supply the fancoil with hot or cold water, which can be used during the summer for pleasant interior cooling and during the winter for providing heat at low costs.

Heat pump inverter air water cooling-en

With 4-way openings, it easily covers even large spaces where air flow is evenly dispersed throughout the room. A cassette unit in the interiors of family houses usually requires lowered ceilings for hidden installation of the working part of the unit. Only the visible panel with adjustable slats, which can be regulated via remote control, is visible from the ceiling.

Simple installation

Installing the unit is simple; just connect to the distribution pipes from the heat pump. The minimum requirement for the lowered ceiling height is only 240mm.

Maximally utilized potential

The heat pump in the CH system can supply cold or hot water to the fancoil. Especially in the summer months, when hot weather can reach interiors, the fancoil ensures a comfortable temperature, which is essential for humans. In the winter months, the fancoil unit can become a better heat source than radiators due to low operating costs.

Main advantages

Automatic flap rotation

3

Three-step modulation

0–10V

External signal

Built-in flood protection

Differences

The difference between a cassette and a wall-mounted unit lies in the direction and distribution of air. The cassette unit distributes air in all directions with less intensity, while the wall-mounted unit distributes air in one direction with the full volume of air flow.

Remote control

Simple control using a controller offers several programs with the possibility of program timing. The fancoil unit can thus be set for certain hours of cooling or heating, what may be suitable precisely for timed cooling of the house from work.

Using the remote control, it is possible to adjust intensity and direction of the cooling/heating air flow. The wall-mounted fancoil unit also offers the possibility of installing a fixed wired wall controller.

Cassette fan coil unit ATTACK FCU-en

Quality components with quiet operation

Efficient air flow, high degree of flow, and low unit noise, thanks to a well-positioned fan motor with a specially designed shape of impeller blades, it achieves very low levels of vibration and noise.

Technical data and documents for download

The cassette fancoil unit with its properties can effectively ensure a comfortable temperature in the house throughout the year. Find out more about other technical data.

loader-icon
  • Quiet operation
  • Automatic flap rotation into the space
  • Three-step modulation
  • Ensures pleasant temperature all year round
  • Power2 – 24 kW
  • Suitable for ATTACK heat pumps
  • Possibility of controlling the unit with an external 0 – 10V signal
  • Built-in flood protection in case of condensate drain blockage
Model (two-pipe system) ATTACK FCU – C 2 ATTACK FCU – C 3 ATTACK FCU – C 4 ATTACK FCU – C 5 ATTACK FCU – C 6 ATTACK FCU – C 8 ATTACK FCU – C 10 ATTACK FCU – C 11 ATTACK FCU – C 12 ATTACK FCU – C 15
Panel DC-MB-SA01M1 DC-MB-SA01M2 DC-MB-SA01M3 DC-MB-SA01M4
Power supply 220V / 50Hz,1 fáza
Air volume flow High m3/h 380 550 680 880 1050 1380 1750 2050 2200 2720
Medium 250 350 400 550 650 850 1050 1250 1300 1650
Low 150 200 250 300 350 500 600 700 750 950
Static pressure Pa 0 0 0 0 0 0 0 0 0 0
Cooling capacity Total High W 2000 3000 3800 4900 5800 7500 9800 11000 12000 15000
Legible W 1400 2200 2850 3500 4250 5500 7150 8250 9100 11175
Total Medium W 1550 2300 2950 3800 4500 5800 7550 8500 9250 11400
Legible W 1050 1600 2100 2600 3150 4100 5350 6150 6850 9000
Total Low W 1100 1650 2100 2700 3200 4150 5400 6100 6650 8250
Legible W 700 1000 1350 1650 2000 2600 3400 3900 4300 6050
Vytápěcí výkon High W 3100 4700 5900 7600 9000 11600 15200 17100 18600 24000
Medium W 2350 3550 4450 5700 6750 8700 11400 12850 13950 18000
Low W 1700 2600 3250 4200 4950 6400 8350 9400 10250 13200
Noise High 0Pa dB(A) 37 39 44 42 45 46 48 50 52 53
Electrical power consumption High 0Pa W 27 32 38 46 65 85 105 125 135 150
Water flow m3/h 0,34 0,51 0,65 0,83 0,99 1,28 1,67 1,87 2,04 2,55
Pressure loss kPa 23 27 26 28 27 26 35 36 42 45
Water connection pipe size Input G3/4″ G3/4″ G3/4″ G3/4″ G3/4″ G3/4″ G3/4″ G3/4″ G3/4″ G3/4″
Output G3/4″ G3/4″ G3/4″ G3/4″ G3/4″ G3/4″ G3/4″ G3/4″ G3/4″ G3/4″
Exchange Type Highly efficient copper tube equipped with aluminum fins with hydrophilic (wetting) surface
Condensate drain hose diameter mm ø26 ø26 ø26 ø26 ø26 ø26 ø26 ø26 ø26 ø26
Dimension Unit L×W×H (mm) 592*592*242 750*750*242 840*840*242 840*840*292 946*946*292
Panel 650*650*40 850*850*40 950*950*40 950*950*40 1050*1050*40
Weight Unit kg 17 18 18 22 23 25 26 27 27 32
Weight Panel kg 2,2 4,2 5 6
“Test conditions:
Two-pipe system
Cooling Inlet air temperature: Dry bulb 27ºC, Wet bulb 19.5ºC
Inlet/outlet water temperature: 7ºC/ 12ºC
Heating Inlet air temperature: 21ºC
Inlet water temperature: 60ºC, same water flow as cooling

High-quality processing

All our products are manufactured with an emphasis on the selection of quality materials and the use of correct technologies and procedures. Quality components ensure maximum product reliability. Our own know-how is a guarantee of reliable service and long life.

fancoil unit attack quality production en

Choose a service partner

Creating a high-quality and prompt service network for our customers is very important to us. Our service partners provide prompt service assistance to every customer throughout the year.

We have a rich service network covering the entire territory of the world

Related products