1,8-10,8 kW
Power
Comfortable temperature
all year round
3
Step modulation
Automatic
Flap rotation
Wall-mounted fancoil units with power from 1.8 – 10.8 kW are suitable for smaller spaces where they ensure a pleasant temperature all year round. It is precisely the heat pump as a source of heat and cold that can supply the fancoil with hot or cold water, which can be used during the summer for pleasant interior cooling and during the winter for providing heat at low costs.
Wall-mounted fancoil unit – its advantages and use
Suitable for spaces where, for layout reasons, the use of another system (cassette) is not possible due to the structural height of the ceiling. As a rule, with the same power parameters, the wall-mounted unit is advantageous compared to the cassette unit, especially in price. Both solutions are qualitatively at the same level; it depends on the design possibilities according to the requirements of the given space.
Simple installation
Installing the unit is simple; just connect to the distribution pipes from the heat pump. Installation in existing spaces has minimal requirements for additional structural modifications.
Maximally utilized potential
The heat pump in the CH system can supply cold or hot water to the fancoil. Especially in the summer months, when hot weather can reach interiors, the fancoil ensures a comfortable temperature, which is essential for humans. In the winter months, the fancoil unit can become a better heat source than radiators due to low operating costs.
Main advantages
Automatic flap rotation
3
Three-step modulation
Differences
The difference between a cassette and a wall-mounted unit lies in the direction and distribution of air. The cassette unit distributes air in all directions with less intensity, while the wall-mounted unit distributes air in one direction with the full volume of air flow.
Remote control
Simple control using a controller offers several programs with the possibility of program timing. The fancoil unit can thus be set for certain hours of cooling or heating, which can be suitable specifically for timed house cooling when coming from work.
Using the remote control, it is possible to adjust intensity and direction of the cooling/heating air flow. The wall-mounted fancoil unit also offers the possibility of installing a fixed wired wall controller.
Quality components with quiet operation
Efficient air flow, high degree of flow, and low unit noise, thanks to a well-positioned fan motor that operates with three-step power modulation and dampens vibrations.
Technical data and documents for download
The wall-mounted fancoil unit with its properties can effectively ensure a comfortable temperature in the house throughout the year. Find out more about other technical data.

- Quiet operation
- Automatic flap rotation into the space
- Three-step modulation
- Ensures pleasant temperature all year round
- Power 1.8 – 10.8 kW
- Suitable for ATTACK heat pumps
| Model (two-pipe system) | ATTACK FCU – W 2 | ATTACK FCU – W 3 | ATTACK FCU – W 4 | ATTACK FCU – W 5 | ATTACK FCU – W 6 | ATTACK FCU – W 8 | |||
| Power supply | 220V / 50Hz 1 fáza | ||||||||
| Air volume flow | High | m3/h | 340 | 510 | 680 | 850 | 1020 | 1360 | |
| Medium | 260 | 380 | 515 | 650 | 765 | 1010 | |||
| Low | 180 | 260 | 340 | 430 | 520 | 700 | |||
| Static pressure | Pa | 0 | 0 | 0 | 0 | 0 | 0 | ||
| Cooling capacity | Total | High | W | 1800 | 2700 | 3600 | 4500 | 5400 | 7200 |
| Legible | W | 1350 | 2025 | 2700 | 3375 | 4050 | 5400 | ||
| Total | Medium | W | 1476 | 2214 | 2952 | 3690 | 4428 | 5904 | |
| Legible | W | 978 | 1399 | 1963 | 2409 | 3044 | 3926 | ||
| Total | Low | W | 1098 | 1647 | 2196 | 2745 | 3294 | 4392 | |
| Legible | W | 649 | 960 | 1355 | 1715 | 2060 | 2710 | ||
| Heating power | High | W | 2700 | 4050 | 5400 | 6750 | 8100 | 10800 | |
| Medium | W | 2146 | 3219 | 4293 | 5366 | 6439 | 8586 | ||
| Low | W | 1512 | 2268 | 3024 | 3780 | 4536 | 6048 | ||
| Noise level | High | 0Pa | dB(A) | 39 | 41 | 42 | 45 | 46 | 47 |
| El. příkon | High | 0Pa | W | 50 | 52 | 60 | 75 | 95 | 130 |
| Water flow | m3/h | 0,31 | 0,46 | 0,62 | 0,77 | 0,93 | 0,93 | ||
| Pressure loss | kPa | 12 | 14 | 17 | 18 | 22,5 | 23,5 | ||
| Water connection pipe size | Input | G1/2″ | G1/2″ | G1/2″ | G1/2″ | G1/2″ | G1/2″ | ||
| Exit | G1/2″ | G1/2″ | G1/2″ | G1/2″ | G1/2″ | G1/2″ | |||
| Exchanger | Type | Highly efficient copper tube equipped with aluminum fins with hydrophilic (wetting) surface | |||||||
| Maximum pressure | MPa | 1,6 | 1,6 | 1,6 | 1,6 | 1,6 | 1,6 | ||
| Condensate drain hose diameter | – | G1/2″ | G1/2″ | G1/2″ | G1/2″ | G1/2″ | G1/2″ | ||
| Dimension | L×W×H | mm | 850×300×198 | 850×300×198 | 970×315×235 | 970×315×235 | 1100×330×235 | 1100×330×235 | |
| Weight | kg | 11 | 11 | 15 | 15 | 20 | 20 | ||
Test conditions: 2-pipe system Cooling
Air inlet temperature: Dry thermometer 27ºC, Wet thermometer 19.5ºC
Inlet/outlet water temperature: 7ºC/ 12ºC
Heating Inlet air temperature: 21ºC
Inlet water temperature: 60ºC, same water flow as for cooling
High-quality processing
All our products are manufactured with an emphasis on the selection of quality materials and the use of correct technologies and procedures. Quality components ensure maximum product reliability. Our own know-how is a guarantee of reliable service and long life.
Choose a service partner
Creating a high-quality and prompt service network for our customers is very important to us. Our service partners provide prompt service assistance to every customer throughout the year.